 How do you calibrate a D. P. transmitter?

The following steps are to be taken which calibrating:

1. Adjust zero of the Xmtrs.

2. Static pressure test: Give equal pressure on both sides of the transmitter.  Zero should not shift. If it is shifting carry out static alignment.

3. Vacuum test: Apply equal vacuum to both the sides. The zero should not shift.

4. Calibration Procedure:

·         Give 20-psi air supply to the transmitter.

·         Vent the L.P. side to atmosphere.

·         Connect output of the Instrument to a standard test gauge. Adjust zero.

5. Apply required pressure to high-pressure side of the transmitter and adjust the span.

6. Adjust zero again if necessary.